N8UE2+3-30 Type 2+3 AC Surge Protection Device

Description

The N8UE2+3-30 is a compact Type 2+3 surge protection device, ideal for protecting sensitive electronic equipment against transient overvoltages caused by switching events and indirect lightning strikes. It features a maximum discharge current of 30kA (8/20μs) , a nominal discharge current of 15kA, and a composite wave open-circuit voltage of 20kV (1.2/50μs) , delivering reliable suppression with a low voltage protection level of 1.5kV. With an ultra-fast response time ≤25ns, it ensures critical loads stay protected. Available in 1P–4P configurations, it mounts on a standard 35mm DIN rail and supports backup fuses up to 125A. The flame-retardant UL 94 V-0 housing and versatile terminals (1.5–35mm² cables) make installation easy and secure. Operates flawlessly from –40℃ to +85℃ and at altitudes up to 5000m. IP20 rated for indoor use.

Technical Data

Operating Temperature Range -40 ℃~85 ℃
Permissible Operating Humidity 5 %~95 %
Atmospheric pressure and altitude -500 m ~ +5000 m
Model NO. N8UE2+3–30
SPD Type Type 2+3
Protection Mode L1/2/3/N-PE
Maximum Continuous Operating Voltage (AC)Uc 275 V
Frequency 50/60 Hz
Nominal Discharge Current In (8/20 μs) 15 kA
Maximum Discharge Current Imax (8/20 μs) 30 kA
composite wave open circuit voltage UOC (1.2/50 μs) 20 kV
Voltage Protection Level Up 1.5 kV
Back-Up Fuse (max) 125 A gL/gG
Response Time tA ≤25 ns
Terminal Screw Torque MC cable: 1.5 mm²~25 mm²
SC cable: 1.5 mm²~35 mm²
Degree of Protection IP 20
Dimensions 1P:82±1mm×18±1mm×66±1mm (L×W×H)
2P:82±1mm×36±1mm×66±1mm (L×W×H)
3P:82±1mm×54±1mm×66±1mm (L×W×H)
4P:82±1mm×72±1mm×66±1mm (L×W×H)
Mounting 35 mm guide rail
Housing material UL 94 V-0

Schematic Diagram

N8UE2+3-30 Surge protector

Outline Dimensions

N8UE2+3-30 Surge protector

Wiring Diagram

N8UE2+3-30 Surge protector